Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
126
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
[1]
Factor for kWh to CO2 conversion
r0043[0...2]
Energy saved [kWh]
-
-
-
-
-
Float 2
Displays calculated energy saved
Index:
[0]
Energy saving in kWh
[1]
Energy saving in currency
[2]
Energy saving in CO2
r0050
CO / BO: Active
command data set
-
-
-
-
-
U16
2
Displays currently active command data set.
0
Command data set 0 (CDS)
1
Command data set 1 (CDS)
2
Command data set 2 (CDS)
Note:
See P0810
r0051[0...1]
CO: Active inverter data
set (DDS)
-
-
-
-
-
U16
2
Displays currently selected and active inverter data set (DDS).
0
Inverter data set 0 (DDS0)
1
Inverter data set 1 (DDS1)
2
Inverter data set 2 (DDS2)
Index:
[0]
Selected inverter data set
[1]
Active inverter data set
Note:
See P0820
r0052.0...15 CO / BO: Active status
word 1
-
-
-
-
-
U16
2
Displays first active status word of inverter (bit format) and can be used to diagnose inverter status.
Bit
Signal name
1 signal
0 signal
00
Inverter ready
Yes
No
01
Inverter ready to run
Yes
No
02
Inverter running
Yes
No
03
Inverter fault active
Yes
No
04
OFF2 active
No
Yes
05
OFF3 active
No
Yes
06
ON inhibit active
Yes
No
07
Inverter warning active
Yes
No
08
Deviation setpoint / act. value
No
Yes
09
PZD control
Yes
No
10
|f_act| >= P1082 (f_max)
Yes
No
11
Warning: Motor current / torque limit
No
Yes
12
Brake open
Yes
No
13
Motor overload
No
Yes
14
Motor runs right
Yes
No
15
Inverter overload
No
Yes
Dependency: r0052 bit 03 "Inverter fault active": Output of bit 3 (Fault) will be inverted on digital output (Low = Fault,
High = No Fault).
Note:
See r2197 and r2198.