Commissioning via the built-in BOP
5.6 Function commissioning
SINAMICS V20 Converter
88
Operating Instructions, 10/2019, A5E34559884-012
OFF3
The braking characteristics of OFF3 are identical with those of OFF1 with the exception of
the independent OFF3 ramp-down time P1135. If the output frequency falls below parameter
value P2167 and if the time in P2168 has expired, then the converter pulses are cancelled
as for the OFF1 command.
Note
•
OFF3 can be entered using a wide range of command sources via BICO parameters
P0848 (BI: 1. OFF3) and P0849 (BI: 2. OFF3).
•
OFF3 is active low.
•
When various OFF commands are selected simultaneously, the following priority applies:
OFF2 (highest priority) – OFF3 – OFF1
5.6.2.2
Running the converter in JOG mode
Functionality
The JOG function can be controlled by either the (built-in) BOP or the digital inputs. When
controlled by the BOP, pressing the RUN button will cause the motor to start and rotate at
the pre-set JOG frequency (P1058). The motor stops when the RUN button is released.
When using the digital inputs as the JOG command source, the JOG frequency is set by
P1058 for JOG right and P1059 for JOG left.