I/O connection
● Create a low-impedance ground connection for additional cabinets, system components,
and distributed devices with the largest possible cross-section (at least 16 mm²).
● Ground unused lines at one end in the cabinet.
● Choose the greatest possible clearance between the power and signal cables (at least 20
cm). The greater the distance over which the cables are routed in parallel, the greater the
clearance must be. You must install additional shields if sufficient clearance cannot be
maintained.
● Avoid unnecessarily long cable loops.
● Surge suppressors – e.g. RC elements or varistors – must be connected to the solenoids of
contactors and relays in the device.
● In order to reduce noise/interference entering or exiting via the cable, filter auxiliary voltages
in the control cabinet.
6.4
Connecting equipotential-bonding conductors
All cabinets belonging to the system are connected by signal cables. Also connect the cabinets
using equipotential-bonding conductors; according to the following diagram, for example:
&ORVHGORRS
FRQWURO
3RZHUXQLW
([FLWDWLRQ
'HPDJQHWL]DWLRQ
(TXLSRWHQWLDOERQGLQJFRQGXFWRU
Figure 6-3
Equipotential bonding conductor
Malfunction as a result of a missing equipotential-bonding conductor
If the control cabinets are not connected to an equipotential-bonding conductor, malfunctions
can occur in the converter.
● Connect all control cabinets involved in meshed drives to an equipotential-bonding
conductor (min. 16 mm
2
). The PE connection provided by the customer is not sufficient.
6.5
Using the equipotential bonding strip and shield bus
Each cabinet is equipped with an equipotential bonding or grounding bar to make it simpler to
connect equipotential bonding conductors.
Connect all internal and external components to this equipotential bonding busbar. is Attach the
shields of incoming and outgoing cables directly to the shield bus. It is important here to
establish the greatest possible area of contact and a good conductive connection.
Electrical connection
6.5 Using the equipotential bonding strip and shield bus
SINAMICS SL150 6SL39616RC100AA02
64
Operating Instructions Rev.201910281458 EXAMPLE