Technical data
4.3 Duty cycles for 4Q applications
SINAMICS DCM DC Converter
42
Operating Instructions, 12/2018, A5E34763375A
4.3
Duty cycles for 4Q applications
Table 4- 3
Duty cycles for 4Q applications
SINAMICS
DCM
6RA80..
Duty cycles
Tu
DC I
continuous
DC II
DC III
DC IV
US rating
Tu = 45 °C
15 min
100%
60 s
150%
15 min
100%
120 s
150%
15 min
100%
10 s
200%
15 min
100%
60 s
150%
°C
A
A
A
A
A
A
A
A
A
400 V, 4Q
.13-6DV62 45
15
13.9
20.8
13.5
20.2
12.6
25.2
13.9
20.8
.18-6DV62 45
30
24.9
37.3
24.2
36.3
22.4
44.8
24.9
37.3
.25-6DV62 45
60
53.1
79.6
51.8
77.7
47.2
94.4
53.1
79.6
.28-6DV62 45
90
78.2
117
76.0
114
72.2
144
78.2
117
.31-6DV62 45
125
106
159
103
155
95.4
190
106
159
.75-6DV62 40
210
164
247
161
242
136
273
157
236
.78-6DV62 40
280
226
340
219
328
201
402
215
323
.81-6DV62 40
400
300
450
292
438
247
494
285
428
.85-6DV62 40
600
470
706
453
680
410
820
450
675
.87-6DV62 40
850
658
987
634
951
579
1159
626
939
.91-6DV62 40
1200
884
1326
857
1286
768
1537
842
1263
.93-4DV62 40
1600
1255
1883
1213
1819
1139
2279
1190
1785
.95-4DV62 40
2000
1477
2216
1435
2152
1326
2653
1404
2106
.98-4DV62 40
3000
2288
3432
2189
3283
2164
4328
2178
3267
480 V, 4Q
.13-6FV62
45
15
13.9
20.8
13.5
20.2
12.6
25.2
13.9
20.8
.18-6FV62
45
30
24.9
37.3
24.2
36.3
22.4
44.8
24.9
37.3
.25-6FV62
45
60
53.1
79.6
51.8
77.7
47.2
94.4
53.1
79.6
.28-6FV62
45
90
78.2
117
76
114
72.2
144
78.2
117
.31-6FV62
45
125
106
159
103
155
95.4
190
106
159
.75-6FV62
40
210
164
247
161
242
136
273
157
236
.78-6FV62
40
280
226
340
219
328
201
402
215
323
.82-6FV62
40
450
320
480
311
466
274
548
306
460
.85-6FV62
40
600
470
706
453
680
410
820
450
675
.87-6FV62
40
850
658
987
634
951
579
1159
626
939
.91-6FV62
40
1200
884
1326
857
1286
768
1537
842
1263