4.6
Line reactors
Line reactors are interfaces on the line side for the Smart Line Modules. These limit line
harmonics to permissible values. This is the reason that you must always use line reactors when
operating Smart Line Modules.
4.6.1
Overview of line reactors
The line reactors listed below must be used for operating the Line Module.
Table 4-5
Overview of line reactors
Line reactors
Article number
Line reactors for S220 Smart Line Modules
16 kW C type
6SL3100-0EE21-6AA0
16 kW D type
6SL5100-0EE21-6AD0
24 kW C type
6SL5100-0EE22-4AC0
24 kW D type
6SL5100-0EE22-4AD0
4.6.2
Safety instructions for line reactors
CAUTION
Burns resulting from high surface temperature of the line reactor
The line reactors can become very hot. You can get seriously burnt when touching the surface.
• Mount the line reactors so that contact is not possible. If this is not possible, attach clearly
visible and understandable warning notices at hazardous positions.
• To prevent adjacent components from suffering damage due to these high temperatures,
maintain a ventilation clearance of 100 mm on all sides of the line reactors.
NOTICE
Damage to the system caused by line reactors that are not permissible
Line reactors that are not permissible can damage the Line Modules.
Line harmonics that damage/disturb other loads connected to the same line supply can also
occur.
• Only use line reactors that are listed in this Equipment Manual.
Line connection and line-side power components
4.6 Line reactors
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
49