Operation
6.6 Control via the operator panel
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
313
6.6.7.7
Lock AOP LOCAL mode
Settings: MENU – Commissioning/Service – AOP settings – Control settings
Save AOP local mode (factory setting: No)
●
Yes: Deactivates the "Control via operator panel" function, thereby disabling the
LOCAL/REMOTE key.
●
No: Activates the LOCAL/REMOTE key.
Note
Lock LOCAL
LOCAL functionality can also be inhibited on the drive by means of the p0806 parameter (BI:
Inhibit master control).
6.6.7.8
Acknowledge error from the AOP
Settings: MENU – Commissioning / Service – AOP Settings – Control Settings
Acknowledging faults at the AOP (factory setting: Yes)
●
Yes: Faults can be acknowledged via the AOP.
●
No: Faults cannot be acknowledged via the AOP.
6.6.7.9
CDS setting via AOP
Settings: MENU – Commissioning/Service – AOP settings – Control settings
CDS changeover via AOP (factory setting: No)
●
Yes: In the LOCAL mode, in the operating screen form the active CDS can the changed
by one. This is helpful, if operation via an AOP would not be possible due to the fact that
a standard telegram is active.
When CDS0 or 2 is active, "CDS+1" switches to CDS1 or CDS3.
When CDS1 or 3 is active, "CDS-1" switches to CDS0 or CDS2.
●
No: In the LOCAL mode, in the operating screen form the active CDS cannot be changed
by one.