![Siemens SINAMICS S Series List Manual Download Page 1372](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271372.webp)
F
u
nct
ion
D
iag
ra
m
s
Ac
tive Infeed
2-
13
72
© Siemens AG
2007 All Rights Reserved
S
IN
A
MICS
S List Manua
l (
L
H1), 0
7
/2007
Fi
gure 2-2
4
4
8
960 – Sign
als and
mon
itoring
functio
n
s, li
ne supp
ly
vol
ta
ge moni
tori
ng (p34
00.0 = 0)
- 8960 -
Function diagram
8
7
6
5
4
3
2
1
fp_8960_01_eng.vsd
DO: A_INF
SINAMICS S
04.07.07 V02.05.00
Active Infeed - Signals and monitoring functions, line supply voltage monitoring (p3400.0 = 0)
85 % 110 %
F06100
"Shutdown due to line supply undervoltage"
A06310
"Supply voltage (p0210) incorrectly parameterized"
p0283 (75 %)
p0282 (85 %)
p0281 (110 %)
A06105
"Line supply undervoltage"
A06301
"Line supply overvoltage"
U_line supply calculated
Supply voltage
p0210
A06300
"Line supply voltage too high when powering-up"
--> voltage cannot be controlled
Monitoring when switching-in the pulses
(regarding the frequency, refer to [8964])
&
Nominal line
supply voltage
Calculated
actual line
supply voltage
[8950.4]
U_line supply after filter
[8960.6]
Vdc_max stat
[8940.4]
U_line supply after filter
[8960.2]
p0115[3] (2000.00 µs)
<1>
<1> For p3400.0 = 1, [8864] applies.
300 ms
Temperature monitor active interface module.
60 s
T
0
F06261
"Temperature in the line filter permanently too high"
X21.2
X21.1
F06260
"Temperature in the line filter too high"
Background
<2>
<2> Only when selecting an AIM (Active Interface Module) in p0220.