Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
21
Installing/mounting
4
4.1
Installation conditions
General installation conditions
When installing the Power Modules carefully observe the conditions listed below in order to
guarantee reliable, continuous and disturbance-free operation.
●
The Power Modules are designed for installation in a control cabinet.
●
The Power Modules are certified for use in environments with degree of pollution 2
without condensation; i.e. in environments where no conductive pollution/dirt occurs.
●
The built-in units fulfill IP20 degree of protection.
●
Devices with push-through technology (PT devices) have IP20 degree of protection,
at the rear of the control cabinet, IP55.
●
You can find the permissible conductor cross-sections for the terminals in:
Connection terminals at the inverter (Page 53)
●
The following section describes how you can install the Power Modules in compliance
with EMC regulations:
EMC-compliant installation of a machine or system (Page 23)
Inverters for systems in the United States / Canada (UL/cUL)
●
For a system configuration in conformance with UL/cUL, use the fuse types approved for
UL/cUL, specified in the Technical data, or the circuit breakers under the following
Internet address.
–
Fuse types: Technical data (Page 65)
–
Circuit breaker
https://support.industry.siemens.com/cs/ww/en/view/109486009
●
The integrated semiconductor short-circuit protection does not provide cable protection.
●
On the system side, provide cable protection in conformance with NEC or CEC, Part 1
and the local regulations.
●
The inverters provide internal motor protection corresponding to UL61800-5-1. The
protection threshold is 115 % of the inverter full load current. When commissioning, you
can adapt the motor overload protection using parameter p0640.
●
For frame size FSF, to connect the line supply and motor only use UL approved ring-type
cable lugs (ZMVV), which are certified for the particular voltage, with a permissible
current of at least 125 % of the input and output current. Use the higher value as basis.