8.16
Output Filters
Output filters are used for the following reasons:
• for down-hole pumping with long cables.
• when shielded output cables are used.
• to avoid any problem with cable reflections.
• to address EMI or DV/DT requirements.
• with the capacitors omitted, the filter can be used as output reactors for synchronous transfer
to limit the current that can circulate while the VFD output is connected to the MV input.
control supports output filters for all control modes.
Output Filter design and operation
The output filter consists of an LC filter used to prevent the output cable dynamics from
interfering with the drive output. It is designed to remove all high frequency components in the
drive output voltage to result in a nearly perfect sinusoidal output waveform.
The output filter adds losses proportional to the square of the RMS output current. The filter
inductance is in series with the VFD output and motor load and can reduce the output voltage
capability, depending on the load power factor. The filter also introduces an amplifying
resonance, which could limit the closed-loop gain for high-performance applications. The filter
consists of series inductors in each phase connected between the drive outputs and the load
(motor) terminals. Shunt capacitors in each phase connect between the load terminals and are
arranged in a floating wye configuration. Capacitors are omitted for closed synchronous transfer
applications.
Having an output filter adds additional concerns with stability and the ability to bypass
redundant cells. The parameter "Permitted Min cell count" (2541) limits the overall number of
cells in bypass, but not their destination.
Advanced Operating Functions
8.16 Output Filters
Control Manual
256
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......