External 5
External 15
Internal AI1
Internal AI11
External 6
External 16
Internal AI2
Internal AI12
External 7
External 17
Internal AI3
External 8
External 18
Internal AI4
External 9
External 19
Internal AI5
Use the pick list variables to assign hardware inputs to internal analog variables used within the code as assigned by the associated
SOP flag selections.
Table 6-71
Analog Output Menu (4660) Parameters for External Outputs
Parameter
ID
Unit
Default
Min
Max
Description
Analog out‐
put #n*
4660+4(n-1)+1
Submenu
Submenu for analog output n (n = 1 to 16).
Analog vari‐
able
4660+4(n-1)+2
Total Cur‐
rent
Set the input source for analog output n.
See Table Pick list for Analog Output Variable Pa‐
rameters.
Output mod‐
ule type
4660+4(n-1)+3
Unip
Set the output type for the module:
• Unip (unipolar)
• Bip (bipolar)
Full range
4660+4(n-1)+4
%
0.0
0.0
300.0
Scale the output range of the selected variable.
*
Each analog output parameter, 1 to 16, contains a submenu consisting of the following
parameters:
• Analog variable
• Output module type
• Full range
The formulas presented in the ID column give you the direct ID number for the corre‐
sponding analog output.
For example, for analog output 4:
• The analog output ID will be 4660 + 4 (4 - 1) + 1, or 4673.
• The analog variable ID for analog output 4 will be 4660 + 4 (4 - 1) + 2, or 4674.
Configuring the External Outputs
Set up the analog outputs via the pick list parameters in the analog output menus, 4661 through
4721, to complete setup:
1. Select the variable to be output to the analog output module from the pick list; all units are
%.
2. Select the type of output, unipolar or bipolar.
3. Select the percent of the value to provide scaling of the variable.
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
Control Manual
144
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......