● For plants and systems distributed over a wide physical area, always use an equipotential
bonding conductor.
● Correctly connect armored cable using a cable gland. The cable armor must be connected
to the cable gland around its complete circumference. The gland itself must be in contact
with the gland plate around its complete circumference and must be connected to PE.
Procedure
&DEOHGXFW
&DEOHWUD\
&
DE
OH
WU
D\
6KLHOGEXVEDU
7UDQVI
'ULYH
0RWRU
6SHHGHQFRGHU
&8
1
Shield connection
2
Cable gland with grounding bushing
Figure 6-4
Shield connection
Input side
Only connect shield 1 on the drive side to the PE shield busbar. Do not connect the shield on
the transformer side.
Output side
Connect shield 1 at the drive to the PE shield busbar. Connect shield 2 at the motor.
6.9
Interconnecting optional connections
Depending on the range of options installed, further connections have to be interconnected.
Detailed information about interconnecting these options with the interfaces is provided in the
circuit manual.
Electrical connection
6.9 Interconnecting optional connections
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
81
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Page 135: ......