The power connections at the input and output of the cells are screw connections located at the
front side of the cells. The screw connections are located in the discharge air flow of the cells.
For systems with mechanical cell bypass, the bypass contactors are located on the front panel
of the cells and lie in the discharge air flow of the cells; this means that all busbars and
contactors are air cooled.
NOTICE
Damage when operated without air cooling
If the drive is operated under no-load conditions, the fan must be ready for operation to
dissipate any component power loss. If no airflow is provided to dissipate the heat, then the
drive and/or its associated components can be damaged. If the medium voltage is switched-
in without there being any airflow, then this causes the coordinated input protection system to
trip.
● After switching-out the medium voltage, allow the fan to run for 10 min to dissipate the
latent heat of the drive.
● Do not switch on the drive without the fan that supplies the airflow being ready for
operation.
The cooling system comprises the following components:
● Fans that are mounted on the drive
● Temperature sensors to monitor the air intake temperature
● Differential pressure monitoring
● Drive for each fan
● Heat exchanger (air/air or air/water)
Heat exchanger
If the drive is equipped with an air-air heat exchanger or an air-water heat exchanger, then
specific instructions and details are provided in the documentation associated with the specific
order.
3.7
Components
Further information is available in the following documents:
● Additional information about connecting the various components is pro‐
vided in the circuit manual.
● You can find information on the interfaces and LEDs of individual com‐
ponents in the "Supplementary component descriptions (
support.industry.siemens.com/cs/ww/en/view/109768128
)" document.
Description
3.7 Components
SINAMICS PERFECT HARMONY GH150 6SL3826
30
Operating Instructions 05/2020
Summary of Contents for SINAMICS PERFECT HARMONY GH150 6SL3826
Page 2: ...19 06 2020 09 25 V14 00 ...
Page 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Page 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Page 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Page 135: ......