3.6.20
dv/dt filter (option L10)
The drive generates pulses at the drive output which have a negative impact on the motor
insulation. The dv/dt filter is used to limit the voltage gradient to max. 1 kV/µs. At the same
time, the dv/dt filter is used to limit the capacitive recharging currents of the motor cables, and
therefore protects the motor insulation system. The dv/dt filter is integrated in the power unit.
①
Drive
②
Motor
R1,R2,R3
6 Ω
dv/dt filter resistance
L1, L2,L3
20 μH
dv/dt filter reactor
C1,C2,C3
1 μF
dv/dt filter capacitor
M
Center of the drive
N
Center point of the dv/dt filter
Figure 3-10 Circuit diagram option L10
Description
3.6 Description of options
SINAMICS GM150 6SL3815-2LN41-4AA2
60
Operating Instructions 04/2017