3.5.12.3
The internal deionized water circuit
The internal water circuit is filled with deionized water (deionized, fully-desalinated water). The
conductivity of the cooling water must be ≤ 1 µS/cm in operation.
NOTICE
Inadmissible additives in the deionized water
Inadmissible additives in the deionized water can cause the cooling system to fail. This could
damage the drive.
● Use only deionized water that corresponds to the specifications. The specification of the
deionized water can be found in the documentation for the re-cooling unit.
Deionized water requirements
Deionized water requirements
Table 3-9
Deionized water requirements
Value
Conductivity during filling
< 10 μS/cm
Evaporation residue
< 20 mg/l
pH value
5 to 9
● Content of metals in the hydrogen sulfide group (lead,
antimony, tin, bismuth, arsenic, copper, cadmium)
● Content of metals from the ammonium sulfide group (iron,
cobalt, nickel, chrome, manganese)
● Content of sulfur chloride and nitrogen compounds
Not detectable
Content of oxidizable, organic substances
Max. a quantity equivalent to the
usage of 30 mg/l potassium per‐
manganate KMnO4
3.5.13
Customer terminal strips
The default setting and interfaces of the customer terminal strips can be found in the circuit
manual. For information about the position of the customer terminal strips within the cabinet,
see the layout diagrams.
See also
Terminal assignments (Page 238)
Description
3.5 Description of the components
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
53
Summary of Contents for SINAMICS GM150
Page 2: ...20 04 2017 13 25 V27 00 ...
Page 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Page 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Page 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Page 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Page 257: ......