Mechanical installation: Checklist
Logbook
Use the following checklist to guide you through the mechanical installation procedure for the
cabinet unit. Read the safety information at the start of these operating instructions before you
start working on the device.
Note
If the option in question is part of the delivery, check this accordingly in the right-hand column.
Check the boxes once you have finished the installation procedure to confirm that the activities
are complete.
Item
Activity
Available / Completed
1
The environmental conditions must be permissible. For more information, see the "Tech‐
nical specifications" section.
If the drive and re-cooling unit are installed separately, the bottom level (switch-off level)
of the expansion tank must be located above the highest water level in the drive.
2
Connect the raw water circuit and the de-ionized water circuit. Remove any contamination
from the piping that may have occurred during shipment or storage.
3
Fill and vent the de-ionized water circuit according to the specifications. Ensure that no
air is trapped in the piping system.
4
Install the separately supplied components. Make the required mechanical and electrical
connections as well as the connection to the de-ionized water circuit.
5
The clearance around an open door (escape route) specified in the applicable accident
prevention guidelines must be observed.
6
For option M13/M78:
Select the required metric gland or PG gland appropriate for the cable cross-section.
Proivde the appropriate holes in the cover plates. When the cable is fed in from above,
ensure that enough room is available if the cable has to be bent because of the cable
feeder and cross-sections. To prevent lateral forces on the entries, insert the cable verti‐
cally.
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
247
Summary of Contents for SINAMICS GM150
Page 2: ...20 04 2017 13 25 V27 00 ...
Page 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Page 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Page 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Page 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Page 257: ......