B.2.4.8
Analog and digital inputs and temperature sensor connections
Table B-22
Power Stack Adapter 2: Analog and digital inputs and temperature sensor connections
Terminal
Designation
Technical specifications
X221
X222
Auxiliary voltage:
Voltage: 24 VDC
Max. total load current of + 24 V auxiliary voltage
of terminals X221 and X222 combined: See note.
Input voltage range:
- 3 V to 30 V
Typical current consumption:
10 mA at 24 VDC
Input delay:
● For "0" to "1": Max. 50 μs
● For "1" to "0": Max. 100 μs
Electrical isolation:
Reference potential is terminal MEXT1 or MEXT2
Level (including ripple):
● High signal level: 15 V to 30 V
● Low signal level: - 3 V to 5 V
1
DI 3
DI 7
2
+24 V (auxiliary voltage)
3
+24 V (auxiliary voltage)
4
DI 2
DI 6
5
DI 1
DI 5
6
+24 V (auxiliary voltage)
7
+24 V (auxiliary voltage)
8
DI 0
DI 4
9
MEXT1 (poten‐
tial-free refer‐
ence for
DI 0, DI 1,
DI 2 and DI 3)
MEXT2 (poten‐
tial-free refer‐
ence for
DI 4, DI 5,
DI 6 and DI 7)
10
M
11
AI 0
AI 1
The analog input can be switched between current
input and voltage input using the S5.0 and S5.1
switches.
Voltage: 0 V to 10 V; Ri > 100 kOhm; resolution
12 bits
Current: 0 mA to 20 mA; Ri = 250 Ohm; resolution
11 bits
12
AI 0-
AI 1-
13
TEMP 0-
TEMP 1-
Two-wire PT100 temperature sensor
14
TEMP 0
TEMP 1
Max. connectable cross-section: 1.5 mm², type: Screw terminal
Note
Maximum load current from the 24 VDC auxiliary voltage and the digital outputs
The total load current through terminals 2, 3, 6, 7 at X221 and X222 of the 24 VDC auxiliary
voltage together with the digital outputs is protected by an internal 4 A fuse. A continuous
current of 3 A in total through this fuse must not be exceeded. In your application, dimension
the total load currents from the eight digital outputs and the terminals of the 24 VDC auxiliary
voltage accordingly.
Technical data and drawings
B.2 Terminal assignments
SINAMICS GM150 6SL3815-2LN41-4AA2
244
Operating Instructions 04/2017
Summary of Contents for SINAMICS GM150
Page 2: ...20 04 2017 13 25 V27 00 ...
Page 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Page 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Page 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Page 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Page 257: ......