Screw type
Set screws and
headless screws
Head screws with
slit
Head screws with
hexagon profile
nm
in - lb
nm
in - lb
nm
in - lb
M3.5
0.5
4.4
1.0
8.9
1.0
8.9
M4
0.8
7.1
1.3
11.5
1.3
11.5
M5
1.0
8.6
2.5
22.1
2.5
22.1
M6
1.3
11.5
3.0
26.6
3.5
31.0
M8
1.8
15.9
3.9
34.5
7.2
63.7
M10
-
-
4.8
42.5
13
115
M12
-
-
-
-
18
159.3
M16
-
-
-
-
30
265.5
Observe the tightening torques of the terminal manufacturer and the test torques according to
DIN EN 60999-1, VED 609-1
Note
A different torque of 8 - 10 Nm is applicable for the M8 screw connection for the PowerCard.
Note
Replacing the current transformer
The current transformer may only be replaced by technicians trained by Siemens.
Note
Defective door interlock system
Contact Customer Support if the door interlock system becomes defective.
See also
9.7.2
Replacing the diode module
The Basic Line Module comprises several diode modules. The diode module is a replaceable
unit. A diode module weighs 13 kg. It takes experienced personnel 20 minutes to replace the
diode rectifier.
Required tools
● 10 mm open-ended wrench or socket wrench
● 13 mm open-ended wrench or socket wrench
● Torque wrench
Maintenance
9.7 Repairs
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
211
Summary of Contents for SINAMICS GM150
Page 2: ...20 04 2017 13 25 V27 00 ...
Page 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Page 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Page 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Page 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Page 257: ......