8.4
Functions
8.4.1
Setpoint channel and closed-loop control
8.4.1.1
Setpoint channel
Setpoint addition
Fine tuning (correction variable) often needs to be carried out on site for applications in which
the command variables are generated by central control systems.
You achieve the correction variable using the addition point for the main and additional setpoint
in the setpoint channel. Both variables are imported simultaneously via two separate or one
setpoint source and added in the setpoint channel.
Adjustable parameters
Parameter
Setting
p1070
Main setpoint
p1071
Main setpoint scaling
r1073
Main setpoint effective
p1075
Supplementary setpoint
p1076
Supplementary setpoint scaling
r1077
Supplementary setpoint effective
r1078
Total setpoint effective
These parameters concern connector inputs to which the setpoint values are connected.
Function diagram
FP 3030
Direction reversal
A reversal of the rotational direction is necessary under the following conditions:
● When the drive should be operated in both directions of rotation.
● If the cables were connected with an incorrect phase sequence.
Note
Note that only one direction of rotation is enabled in the factory setting.
Operation
8.4 Functions
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
163
Summary of Contents for SINAMICS GM150
Page 2: ...20 04 2017 13 25 V27 00 ...
Page 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Page 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Page 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Page 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Page 257: ......