Keyboard test
Use this menu to test the function of each individual key of the AOP. Keys that you press are
represented on a symbolic keyboard on the display. You can press the keys in any order you
wish. If each key has been pressed at least once, you can exit the menu by pressing the <Back>
key.
You can also exit the "Keyboard test" menu by pressing and holding any key.
LED test
Use this menu to test the function of the AOP LEDs.
Flash FS formatting
The drive reads the ACX files to describe the parameters and alarms. The ACX files are
buffered in the Flash File System. The data is deleted after being parsed.
To rule out the risk of files being retained, the Flash File System can be manually deleted via
this menu item.
Note
The Flash memory is formatted, without further confirmation, after pressing the <OK> function
key.
Note
The CompactFlash card is not formatted.
Delete persistent database
The database with all parameter and alarm descriptions of the found topology is stored in the
battery-buffered RAM. The database is available immediately after a power off and on of the
supply voltage.
The "Delete persistent database" menu item deletes the database manually. The database
will be rebuilt during the next power up.
Note
The database is deleted immediately, without further confirmation, after pressing the <OK>
function key.
Operation
8.2 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3815-2LN41-4AA2
160
Operating Instructions 04/2017
Summary of Contents for SINAMICS GM150
Page 2: ...20 04 2017 13 25 V27 00 ...
Page 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Page 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Page 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Page 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Page 257: ......