![Siemens Sinamics GM150 6SL3835-2LN44-2AA0 Operating And Installation Instructions Download Page 94](http://html.mh-extra.com/html/siemens/sinamics-gm150-6sl3835-2ln44-2aa0/sinamics-gm150-6sl3835-2ln44-2aa0_operating-and-installation-instructions_378208094.webp)
Figure 6-4
Grounding lug
6.5.3
Preparations for connecting the power cables
● Disconnect the cabinets from the power supply.
● Ensure that all the necessary safety measures have been taken at the installation location.
● Allow unimpeded access to the cable clamping bar in the cabinets.
6.5.4
Connecting power cables
①
Contact surface
Figure 6-5
Example: Connecting the power cables
1. Clean the contact surfaces immediately before screwing the connections. Use spirit and a
lintless cloth for cleaning.
2. Apply a thin film of grease. Electrolube 2G is a suitable lubricator.
3. Screw the cable lug with a M12 screw and, if necessary, with a washer to the contact
surface. Tighten the nuts with a torque of 50 Nm.
Electrical connection
6.5 Connection
SINAMICS GM150 6SL3835-2LN44-2AA0
94
Operating Instructions Rev.201910281250 MUSTER