
9.3
System runtime
Overview
By evaluating the system runtime of the converter, you can decide when you should replace
components subject to wear in time before they fail - such as fans, motors and gear units.
Function description
The system runtime is started as soon as the Control Unit power supply is switched-on. The
system runtime stops when the Control Unit is switched off.
The system runtime comprises r2114[0] (milliseconds) and r2114[1] (days):
System runtime = r2114[1] × days + r2114[0] × milliseconds
If r2114[0] has reached a value of 86,400,000 ms (24 hours), r2114[0] is set to the value 0 and
the value of r2114[1] is increased by 1.
Example
Parameter
Description
r2114[0]
System runtime (ms)
r2114[1]
System runtime (days)
You cannot reset the system runtime.
Parameters
Parameter
Description
Factory setting
r2114[0 … 1]
Total system runtime
-
Warnings, faults and system messages
9.3 System runtime
SINAMICS G120XA converter
746
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......