Dependency:
The following applies: p2191< p2168 if p2168 <> 0
See also: p2181, p2182, p2184, p2193
See also: A07892, F07895, A07926
Note
For the setting p2191 = 0, the monitoring for dry running operation or belt breakage is deactivated.
Pre-assignment: p2191 = 5 % of the rated motor torque (p0333).
p2192[0...n]
Load monitoring delay time / Load monit t_del
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
0.00 [s]
Max:
65.00 [s]
Factory setting:
10.00 [s]
Description:
Sets the delay time to evaluate the load monitoring.
p2193[0...n]
Load monitoring configuration / Load monit config
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
0
Max:
5
Factory setting:
1
Description:
Sets the load monitoring configuration.
Value:
0:
Monitoring switched out
1:
Monitoring torque and load drop
2:
Monitoring speed and load drop
3:
Monitoring load drop
4:
Monitoring pump and load failure
5:
Monitoring fan and load failure
Dependency:
See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925, F07936
Note
p2193 = 4, 5 can only be combined with p2181 = 7, 8.
r2197.0...13
CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2534
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the first status word of the monitoring functions.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
|n_act| <= n_min p1080
Yes
No
8022
01
|n_act| <= speed threshold value 2 p2155
Yes
No
8010
02
|n_act| > speed threshold value 2 p2155
Yes
No
8010
03
n_act >= 0
Yes
No
8011
04
|n_act| >= n_set
Yes
No
8022
05
|n_act| <= n_standstill p1226
Yes
No
8022
06
|n_act| > n_max
Yes
No
8010
Parameters
7.3 Parameters
SINAMICS G120XA converter
600
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB