Note
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset is completed with p0970 = 0 and r3996[0] = 0.
The following generally applies:
One index of parameters p2100, p2101, p2118, p2119, p2126, p2127 is not reset, if a parameterized message is
precisely active in this index.
p0971
Save parameters / Save par
Access level: 1
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
30
Factory setting:
0
Description:
Setting to save parameters in the non-volatile memory.
When saving, only the adjustable parameters intended to be saved are taken into account.
Value:
0:
Inactive
1:
Save drive object
10:
Save in non-volatile memory as setting 10
11:
Save in non-volatile memory as setting 11
12:
Save in non-volatile memory as setting 12
30:
State when delivered, save in non-volatile memory as setting 30
Dependency:
See also: p0970, p1960, r3996
CAUTION
If a memory card (optional) is inserted – and the USB interface is not used, the following applies:
The parameters are also saved on the card and therefore overwrite any existing data!
NOTICE
The Control Unit power supply may only be switched off after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
For p0971 = 30:
The original state when delivered is overwritten when executing this memory function.
Note
Parameters saved with p0971 = 10, 11, 12 can be loaded again with p0970 = 10, 11 or 12.
Identification and maintenance data (I&M data, p8806 and following) are only saved for p0971 = 1.
p0972
Drive unit reset / Drv_unit reset
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Description:
Sets the required procedure to execute a hardware reset for the drive unit.
Value:
0:
Inactive
1:
Hardware-Reset immediate
2:
Hardware reset preparation
3:
Hardware reset after cyclic communication has failed
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
459