00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Enable operation
Yes
No
-
04
Enable ramp-function generator
Yes
No
-
05
Continue ramp-function generator
Yes
No
-
06
Enable speed setpoint
Yes
No
-
08
Jog 1
Yes
No
3001
09
Jog 2
Yes
No
3001
10
Master control by PLC
Yes
No
-
Note
OC: Operating condition
r0899.0...11
CO/BO: Status word sequence control / ZSW seq_ctrl
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2503
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the status word of the sequence control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ready for switching on
Yes
No
-
01
Ready
Yes
No
-
02
Operation enabled
Yes
No
-
03
Jog active
Yes
No
-
04
No coasting active
OFF2 inactive
OFF2 active
-
05
No Quick Stop active
OFF3 inactive
OFF3 active
-
06
Switching on inhibited active
Yes
No
-
07
Drive ready
Yes
No
-
08
Controller enable
Yes
No
-
09
Control request
Yes
No
-
11
Pulses enabled
Yes
No
-
Note
For bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
r0944
CO: Counter for fault buffer changes / Fault buff change
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8060
Min:
-
Max:
-
Factory setting:
-
Description:
Display and connector output for the counter for changes of the fault buffer.
This counter is incremented every time the fault buffer changes.
Recommendation:
Used to check whether the fault buffer has been read out consistently.
Dependency:
See also: r0945, r0947, r0948, r0949, r2109
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
455
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......