Note
The following status bits are displayed in r0053:
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
Bit 03: r2197 Bit 8
Bit 04: r2197 Bit 2
Bit 05: r2197 Bit 1
Bit 06: r2197 Bit 4
Bit 07: r2197 Bit 9
Bit 08: r2197 Bit 10
Bit 09: r1199 Bit 2 (negated)
Bit 10: r2349 Bit 10
Bit 11: r2349 Bit 11
r0053.0...11
CO/BO: Status word 2 / ZSW 2
CUG120XA_USS (DC
braking)
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for status word 2.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DC braking active
Yes
No
-
01
|n_act| > p1226 (n_standstill)
Yes
No
-
02
|n_act| > p1080 (n_min)
Yes
No
-
03
I_act >= p2170
Yes
No
-
04
|n_act| > p2155
Yes
No
-
05
|n_act| <= p2155
Yes
No
-
06
|n_act| >= r1119 (n_set)
Yes
No
-
07
Vdc <= p2172
Yes
No
-
08
Vdc > p2172
Yes
No
-
09
Ramp-up/ramp-down completed
Yes
No
-
10
Technology controller output at the lower limit
Yes
No
-
11
Technology controller output at the upper limit
Yes
No
-
NOTICE
p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
Note
The following status bits are displayed in r0053:
Bit 00: r1239 Bit 8
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
Bit 03: r2197 Bit 8
Bit 04: r2197 Bit 2
Bit 05: r2197 Bit 1
Bit 06: r2197 Bit 4
Bit 07: r2197 Bit 9
Bit 08: r2197 Bit 10
Bit 09: r1199 Bit 2 (negated)
Bit 10: r2349 Bit 10
Bit 11: r2349 Bit 11
Parameters
7.3 Parameters
SINAMICS G120XA converter
366
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB