7.3
Parameters
All objects: CUG120XA_USS
r0002
Drive operating display / Drv op_display
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
200
Factory setting:
-
Description:
Operating display for the drive.
Value:
0:
Operation - everything enabled
10:
Operation - set "enable setpoint" = "1" (p1142)
12:
Operation - RFG frozen, set "RFG start" = "1" (p1141)
13:
Operation - set "enable RFG" = "1" (p1140)
14:
Operation - MotID, excitation running
16:
Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
17:
Operation - braking with OFF3 can only be interrupted with OFF2
18:
Operation - brake on fault, remove fault, acknowledge
19:
Operation - DC braking active (p1230, p1231)
21:
Ready for operation - set "Enable operation" = "1" (p0852)
22:
Ready for operation - de-magnetizing running (p0347)
31:
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
35:
Switching on inhibited - carry out first commissioning (p0010)
41:
Switching on inhibited - set "ON/OFF1" = "0" (p0840)
42:
Switching on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
43:
Switching on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
44:
Switching on inhibited - supply STO terminal w/ 24 V (hardware)
45:
Switching on inhibited - remove fault, acknowledge fault
46:
Switching on inhibited - exit commissioning mode (p0010)
70:
Initialization
200:
Wait for booting/partial booting
Dependency:
See also: r0046
NOTICE
For several missing enable signals, the corresponding value with the highest number is displayed.
Note
OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
p0003
Access level / Acc_level
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C1, T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
3
Max:
4
Factory setting:
3
Description:
Sets the access level to read and write parameters.
Value:
3:
Expert
Parameters
7.3 Parameters
SINAMICS G120XA converter
352
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB