6.2.2.4
Analog inputs
Function description
S>@
$,
$,
U>@
&,S\\\\
S>@
$,
$,
U>@
&,S\\\\
Define the analog input type
With parameter p0756[x] you specify the type of analog input.
Table 6-4
Default settings via parameter p0756
AI 0 Unipolar voltage input
0 V … +10 V
p0756[0] = 0
Unipolar voltage input monitored
+2 V … +10 V
1
Unipolar current input
0 mA … +20 mA
2
Unipolar current input monitored
+4 mA … +20 mA
3
Bipolar voltage input (factory setting)
‑10 V … +10 V
4
AI 1 Unipolar voltage input
0 V … +10 V
p0756[1] = 0
Unipolar voltage input monitored
+2 V … +10 V
1
Unipolar current input
0 mA … +20 mA
2
Unipolar current input monitored
+4 mA … +20 mA
3
Bipolar voltage input (factory setting)
‑10 V … +10 V
4
Defining the function of an analog input
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the particular analog input via its index, e.g.
parameter p0755[0] is assigned to analog input 0.
Example
$, U>@ >@
S
In order to enter the supplementary setpoint via analog input AI 0, you must interconnect AI 0
with the signal source for the supplementary setpoint.
Set p1075 = 755[0].
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
139