r29549
CO/BO: Multi-pump control feedback signal for contactor / Mpc fdb signal
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Bico to p1269[0] as a feedback signal
p29570[0...n]
Ramp-up scaling 1 / RmpUpScaling1
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [%]
Max:
9999999.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the ramp-up scaling 1 for the dual ramp function [%].
Note
The linear acceleration time from speed 0 to speed p29571 can be calculated via formula
(p29571/p1082)*p1120*p29570.
If p1130 is not equal to 0, the time will be adapted.
p29571[0...n]
Threshold speed 2 / Thresh_2_Ramp
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: -
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
30.00 [rpm]
Description:
Defines the threshold 2 for comparing the speed actual value with the speed threshold.
p29572[0...n]
Ramp-up scaling 2 / RmpUpScaling2
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [%]
Max:
9999999.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the ramp-up scaling 2 for the dual ramp function [%].
Note
The linear acceleration time from speed p29571 to constant speed V can be calculated via formula
((V-p29571)/p1082)*p1120*p29572.
If p1130 is not equal to 0, the time will be adapted.
p29573[0...n]
Ramp-down scaling 1 / RmpDnScaling1
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [%]
Max:
9999999.00 [%]
Factory setting:
100.00 [%]
Description:
Defines the ramp-down scaling 1 for the dual ramp function [%].
Parameters
7.2 Parameter list
SINAMICS G120X converter
922
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC