p2312
Technology controller Kp adaptation upper value / Kp adapt upper val
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.000
Max:
1000.000
Factory setting:
10.000
Description:
Sets the upper value for the adaptation of proportional gain Kp for the technology controller.
Dependency:
See also: p2310, p2311, p2313, p2314, p2315, r2316
CAUTION
The upper value must be set higher than the lower value (p2312 > p2311).
Note
Kp adaptation is activated with p2252.7 = 1.
p2313
Technology controller Kp adaptation lower starting point / Kp adapt lower pt
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
0.00 [%]
Description:
Sets the lower starting point for the adaptation of proportional gain Kp for the technology controller.
Dependency:
See also: p2310, p2311, p2312, p2314, p2315, r2316
CAUTION
The upper starting point must be set higher than the lower starting point (p2314 > p2313).
Note
Kp adaptation is activated with p2252.7 = 1.
p2314
Technology controller Kp adaptation upper starting point / Kp adapt upper pt
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.00 [%]
Max:
400.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the upper activation point for the adaptation of proportional gain Kp for the technology controller.
Dependency:
See also: p2310, p2311, p2312, p2313, p2315, r2316
CAUTION
The upper starting point must be set higher than the lower starting point (p2314 > p2313).
Note
Kp adaptation is activated with p2252.7 = 1.
p2315
CI: Technology controller Kp adaptation scaling signal source / Kp adapt scal s_s
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source to scale the results of the adaptation of the proportional gain Kp for the technology controller.
Parameters
7.2 Parameter list
SINAMICS G120X converter
810