Dependency:
See also: p2257
Note
The ramp-down time is referred to 100 %.
r2260
CO: Technology controller setpoint after ramp-function generator / Tec_ctr set aftRFG
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: 9_1
Unit selection: p0595
Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Sets the setpoint after the ramp-function generator of the technology controller.
p2261
Technology controller setpoint filter time constant / Tec_ctrl set T
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
0.000 [s]
Description:
Sets the time constant for the setpoint filter (PT1) of the technology controller.
r2262
CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: 9_1
Unit selection: p0595
Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Display and connector output for the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
p2263
Technology controller type / Tec_ctrl type
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the type of technology controller.
Value:
0:
D component in the actual value signal
1:
D component in system deviation
p2264[0...n]
CI: Technology controller actual value / Tec_ctrl act val
Access level: 2
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the actual value of the technology controller.
Parameters
7.2 Parameter list
SINAMICS G120X converter
802