p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
30.000 [s]
Factory setting:
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
30.000 [s]
Factory setting:
0.500 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
30.000 [s]
Factory setting:
0.000 [s]
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1138[0...n]
CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
See also: p1120
Note
The ramp-up time is set in p1120.
p1139[0...n]
CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency:
See also: p1121
Note
The ramp-down time is set in p1121.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC