r0965
PROFIdrive profile number / PD profile number
G120X_DP,
G120X_PN
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the PROFIdrive profile number and profile version.
Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note
When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
p0969
System runtime relative / t_System relative
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8060
Min:
0 [ms]
Max:
4294967295 [ms]
Factory setting:
0 [ms]
Description:
Displays the system runtime in ms since the last POWER ON.
Note
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
p0970
Reset drive parameters / Drive par reset
Access level: 1
Calculated: -
Data type: Unsigned16
Can be changed: C2(1, 30)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
300
Factory setting:
0
Description:
The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
Value:
0:
Inactive
1:
Start a parameter reset
3:
Start download of volatile parameters from RAM
10:
Start loading the parameters saved with p0971=10
11:
Start loading the parameters saved with p0971=11
12:
Start loading the parameters saved with p0971=12
30:
Start loading the delivery state saved with p0971=30
100:
Start a BICO interconnection reset
300:
Only Siemens internal
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Parameters
7.2 Parameter list
SINAMICS G120X converter
602
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC