p0096
Application class / Appl_class
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6019
Min:
0
Max:
2
Factory setting:
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
Expert
2:
Dynamic Drive Control (DDC)
Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on the
power unit that is connected (Power unit is more than 18KW, p0096=2. Power unit is less than 18KW, p0096=1).
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
Note
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor data
identification as well as the setting of the operating mode and parameterization of the closed-loop control must be
appropriately adapted.
p0100
IEC/NEMA Standards / IEC/NEMA Standards
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1, 2)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
2
Factory setting:
0
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in [kW]
or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value:
0:
IEC (50 Hz line, SI units)
1:
NEMA (60 Hz line, US units)
2:
NEMA (60 Hz line, SI units)
Dependency:
If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
See also: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0337, p1800
Note
The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
p0124[0...n]
CU detection via LED / CU detection LED
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: T, U
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Identification of the Control Unit using an LED.
Parameters
7.2 Parameter list
SINAMICS G120X converter
498