r0087
CO: Actual power factor / Cos phi act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
r0089[0...2]
Actual phase voltage / U_phase act val
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: 5_3
Unit selection: p0505
Function diagram: 6730
Min:
- [V]
Max:
- [V]
Factory setting:
- [V]
Description:
Displays the actual phase voltage.
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
Note
The values are determined from the transistor switch-on duration.
p0096
Application class / Appl_class
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6019
Min:
0
Max:
2
Factory setting:
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
Expert
1:
Standard Drive Control (SDC)
2:
Dynamic Drive Control (DDC)
Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on the
power unit that is connected (Power unit is more than 18KW, p0096=2. Power unit is less than 18KW, p0096=1).
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
The following applies for p0096 = 1:
The motor type (p0300) synchronous or reluctance motor is not possible.
Note
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor data
identification as well as the setting of the operating mode and parameterization of the closed-loop control must be
appropriately adapted.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
497