Description:
Display and connector output for the energy values at the output terminals of the power unit.
Index:
[0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency:
See also: p0043
Note
The signal can be displayed as process variable (scaling: 1 = 1 Wh).
This is enabled in p0043.
The display is also reset with p0040 = 1.
If an enable is present in r0043 when the Control Unit powers up, then the value from r0039 is transferred into r0042.
As r0039 serves as a reference signal for r0042, due to format reasons, the process energy display can only process
values of r0039 up to 2147483 kWh. r0039 should also be reset using this value.
p0043
BI: Enable energy usage display / Enab energy usage
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to enable/reset the process energy display in r0042.
BI: p0043 = 1 signal:
The process energy display is enabled in r0042.
Dependency:
See also: r0042
p0045
Display values smoothing time constant / Disp_val T_smooth
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6799
Min:
0.00 [ms]
Max:
10000.00 [ms]
Factory setting:
4.00 [ms]
Description:
Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
r0046.0...31
CO/BO: Missing enable signal / Missing enable sig
Access level: 1
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2634
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for missing enable signals that are preventing the closed-loop drive control from being
commissioned.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
OFF1 enable missing
Yes
No
7954
01
OFF2 enable missing
Yes
No
-
02
OFF3 enable missing
Yes
No
-
03
Operation enable missing
Yes
No
-
04
DC braking enable missing
Yes
No
-
08
Safety enable missing
Yes
No
-
10
Ramp-function generator enable missing
Yes
No
-
11
Ramp-function generator start missing
Yes
No
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
481