6.10.3
Bypass
Overview
The "Bypass" function switches the motor between converter and line operation.
.
.
.
.
.
'212
'2&20
'212
'2&20
',
',
9287
*1'
.
.
.
U
%,S>@
U
%,S>@
S
U
S
U
Figure 6-97
Bypass control via converter
Requirements
● The "Bypass" function is supported only for induction motors.
● The K1 converter contactor and K2 line contactor are designed for switching under load.
● The K2 line contactor is designed for switching under inductive load.
● The K1 converter contactor and K2 line contactor are interlocked against closing at the
same time.
● The "flying restart" function must be activated (p1200 = 1 or 4).
Flying restart – switching on while the motor is running (Page 423)
$
%
&