6.10
Energy saving
6.10.1
Efficiency optimization
Overview
The efficiency optimization reduces the motor losses as far as possible.
Active efficiency optimization has the following advantages:
● Lower energy costs
● Lower motor temperature rise
● Lower motor noise levels
Active efficiency optimization has the following disadvantage:
● Longer acceleration times and more significant speed dips during torque surges.
The disadvantage is only relevant when the motor must satisfy high requirements relating to the
dynamic performance. Even when efficiency optimization is active, the converter closed-loop
motor control prevents the motor from stalling.
Precondition
Efficiency optimization functions under the following preconditions:
● Operation with an induction motor
● Vector control is set in the converter.
Function description
'ULYHQPDFKLQH
,QYHUWHU
6SHHG
6SHHG
VSHFLILHG
9DULDEOH
)OX[
7RUTXH
Figure 6-92
Efficiency optimization by changing the motor flux
The three variables that the converter can directly set, which define efficiency of an induction
motor, are speed, torque and flux.
$
%
&
Advanced commissioning
6.10 Energy saving
SINAMICS G120X converter
434
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC