Parameter Object, Instance Number: 401 hex
Supported services
Class
● Get Attribute all
Instance ● Get Attribute all
● Set Attribute single
Table 6-40
Class Attribute
No.
Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Cyclic communication is established via parameter object 401.
Example: Read parameter 2050[10] (connector output to interconnect the PZD received from
the fieldbus controller)
Get Attribute single function with the following values:
● Class = 401 hex
● Instance = 2050 = 802 hex corresponds to the parameter number
● Attribute = 10 = A hex corresponds to index 10
Example: Parameter 1520[0] writing (upper torque limit)
Set Attribute single function with the following values:
● Class = 401 hex
● Instance = 1520 = 5F0 hex corresponds to the parameter number
● Attribute = 0 = 0 hex corresponds to index 0
● Data = 500.0 (value)
Supported ODVA AC/DC assemblies
Overview
Number
required/
optional
Type
Name
hex
dec
14 hex
20
Required
Sending
Basic Speed Control Output
46 hex
70
Required
Receiving
Basic Speed Control Input
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
239