Defining the function of an analog input
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the particular analog input via its index, e.g.
parameter p0755[0] is assigned to analog input 0.
Connector inputs are designated in the parameter list with the prefix "CI".
Example
$, U>@ >@
S
In order to enter the supplementary setpoint via analog input AI 0, you must interconnect AI 0
with the signal source for the supplementary setpoint.
Set p1075 = 755[0].
Parameters
Table 6-5
Frequently used connector inputs (CI) of the converter
Parameter
Description
Factory setting
p1070[C]
CI: Main setpoint
Dependent on the converter
p1075[C]
CI: Supplementary setpoint
0
p2253[C]
CI: Technology controller setpoint 1
0
p2264[C]
CI: Technology controller actual value
0
You can find additional connector inputs in the parameter list.
Parameter list (Page 470)