Table 6-2
Commands for switching the motor on and off
ON
Jogging 1
Jogging 2
Enable opera‐
tion
The converter switches the motor on.
OFF1, OFF3
1. The converter brakes the motor.
2. The converter switches off the motor once it comes to a standstill.
The converter identifies that the motor is at a standstill when at least one of the following
conditions is satisfied:
● The speed actual value falls below the threshold in p1226, and the time started in
p1228 has expired.
● The speed setpoint falls below the threshold in p1226, and the time subsequently
started in p1227 has expired.
OFF2
Inhibit opera‐
tion
The converter switches off the motor immediately without first braking it.
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
184
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC