![Siemens SINAMICS G120P Operating Instructions Manual Download Page 354](http://html.mh-extra.com/html/siemens/sinamics-g120p/sinamics-g120p_operating-instructions-manual_378189354.webp)
Functions
7.4 Setpoint calculation
Inverter cabinet units
354
Operating Instructions, 12/2014, A5E32923362A
Table 7- 20 Additional parameters to set the extended ramp-function generator
Parameter
Description
p1120
Ramp-function generator, ramp-up time (factory setting: 20 s)
Accelerating time in seconds from zero speed up to the maximum speed p1082
p1121
Ramp-function generator, ramp-down time (factory setting: 30 s)
Braking time in seconds from the maximum speed down to standstill
p1130
Ramp-function generator initial rounding time (factory setting: 2 s)
Initial rounding for the extended ramp-function generator. The value applies to ramp
up and ramp down.
p1131
Ramp-function generator final rounding time (factory setting: 2 s)
Final rounding for the extended ramp-function generator. The value applies to ramp
up and ramp down.
p1134
Ramp-function rounding type (factory setting: 0)
0: Continuous smoothing
1: Discontinuous smoothing
p1135
OFF3 ramp-down time (factory setting 3 s)
The quick stop (OFF3) has its own ramp-down time.
p1136
OFF3 initial rounding time (factory setting: 0.5 s)
Initial rounding for OFF3 for the extended ramp-function generator.
p1137
OFF3 final rounding time (factory setting: 0 s)
Final rounding for OFF3 for the extended ramp-function generator.
You can find more information in function diagram 3070 and in the parameter list of the List
Manual.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......