Commissioning
5.3 Commissioning with the IOP
Inverter cabinet units
136
Operating Instructions, 12/2014, A5E32923362A
5.3.3
Basic commissioning with IOP
"Basic commissioning" wizard
The "Basic commissioning" wizard described below applies to Control Units as of software
version 4.4.
Procedure
Proceed as follows to perform the basic commissioning of the inverter with the IOP:
0. Select "Basic commissioning..." in the "Wizard" menu.
1. Select "Yes" or "No" to reset to the factory settings.
The factory settings are reset before all parameter
changes made during the basic commissioning have
been saved.
2. Select the control type for the connected motor.
3. Select the motor data for your inverter and the con-
nected motor.
This data is required to calculate the correct speed and
the displayed values for the application.