Characteristics after selecting the application class Standard Drive Control
Selecting application class Standard Drive Control reduces the number of characteristics and
the setting options:
● A linear and a parabolic characteristic are available.
● Selecting a technological application defines the characteristic.
● The following cannot be set - ECO mode, FCC, the programmable characteristic and a
specific voltage setpoint.
I
VHW
8
VHW
I
VHW
,
TBVHW
,
TBVHW
0D[LPXPRXWSXW
YROWDJH
7HFKQRORJLFDODSSOLFDWLRQ
5DWHGPRWRUIUHTXHQF\
/LQHDU
3DUDEROLF
S
S
S
U
U
①
The closed-loop starting current control optimizes the speed control at low speeds
②
The inverter compensates the voltage drop across the motor stator resistance
Figure 6-48 Characteristics after selecting Standard Drive Control
Table 6-50
Linear and parabolic characteristics
Requirement
Application examples
Remark
Character‐
istic
Parameter
The required torque is in‐
dependent of the speed
Conveyor belts, roller conveyors, chain
conveyors, eccentric worm pumps, com‐
pressors, extruders, centrifuges, agita‐
tors, mixers
-
Linear
p0501 = 0
The required torque in‐
creases with the speed
Centrifugal pumps, radial fans, axial fans Lower losses in the motor
and inverter than for a lin‐
ear characteristic.
Parabolic p0501 = 1
Additional information on the characteristics can be found in the parameter list and in the
function diagrams 6851 ff of the List Manual.