Parameter
Description
p0779
x coordinate of the 2nd characteristic point [% of p200x]
p0780
y coordinate of the 2nd characteristic point [V or mA]
Setting the characteristic
You must define your own characteristic if none of the default types match your particular
application.
Example:
Via analog output 0, the inverter should convert a signal in the value range 0 % … 100 % into
an output signal 6 mA … 12 mA.
Procedure
&XUUHQWRXWSXWP$P$
P$
[
S
\
S
[
S
\
S
Set the following parameters to set the characteristic to
match the example:
1. Set p0776[0] = 2
This defines analog output 0 as a current output.
2. Set p0777[0] = 0.0 (x1)
3. Set p0778[0] = 6.0 (y1)
4. Set p0779[0] = 100.0 (x2)
5. Set p0780[0] = 12.0 (y2)
Defining the function of an analog output
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the particular analog output via its index,
e.g. parameter p0771[0] is assigned to analog output 0.
Table 6-7
Connector outputs (CO) of the inverter (selection)
CO
Meaning
CO
Meaning
r0021 Actual speed smoothed
r0026 DC link voltage smoothed
r0024 Output frequency, smoothed
r0027 Absolute actual current smoothed
r0025 Output voltage smoothed
A complete list of the connector outputs is provided in the List Manual.
Additional information is provided in the parameter list and in function diagram 2261 of the List
Manual.
Overview of the manuals (Page 459)