● [11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
● [12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
Calculating the motor parameters: Select "Complete calculation".
Set the check mark for "RAM to ROM (save data in the drive)" to save your data in the inverter
so that it is not lost when the power fails.
Select "Finish".
Figure 5-16 Exiting quick commissioning in STARTER
Figure 5-17 Exiting quick commissioning in Startdrive
You have completed quick commissioning.
Select a suitable control mode
Control mode
U/f control or flux current control (FCC)
Encoderless vector control
Motors that can be
operated
Induction motors
Induction and synchronous motors
Application exam‐
ples
● Pumps, fans, and compressors with flow
characteristic
● Wet or dry blasting technology
● Mills, mixers, kneaders, crushers, agitators
● Horizontal conveyor technology (conveyor
belts, roller conveyors, chain conveyors)
● Basic spindles
● Pumps and compressors with displacement
machines
● Rotary furnaces
● Extruder
● Centrifuges
Commissioning
5.5 Quick commissioning with a PC
SINAMICS G120C converter
146