To assign the device name, you need an engineering software, e.g. HW-Config or STARTER.
The inverter saves the device name on the inserted memory card.
IP address
In addition to the device name, PROFINET also uses an IP address.
You have the following options to specify the IP address of the inverter:
● You specify the IP address via an engineering software, e.g. via HW-Config or STARTER.
● The IO Controller assigns an IP address to the inverter.
Telegram
Set the same telegram in the inverter as in the IO Controller. Interconnect the telegrams in the
control program of the IO Controller with the signals of your choosing.
Drive control via PROFIBUS or PROFINET (Page 179)
Application examples
You can find application examples for PROFINET communication on the Internet:
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
PROFINET, with Safety Integrated (via terminal) and HMI (
support.industry.siemens.com/cs/ww/en/view/60441457
Controlling the speed of a SINAMICS G110M/G120 (Startdrive) with S7-1500 (TO) via
PROFINET, with Safety Integrated (via terminal) and HMI (
support.industry.siemens.com/cs/ww/en/view/78788716
4.9.9.4
Installing GSDML
Procedure
To install the GSDML of the inverter in the engineering system of the controller, proceed as
follows:
1. Save the GSDML to your PC .
https://support.industry.siemens.com/cs/ww/en/view/
– From your inverter:
Insert a memory card into the inverter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
2. Unzip the GSDML file on your computer.
3. Import the GSDML into the engineering system of the controller.
You have now installed the GSDML in the engineering system of the controller.
Installing
4.9 Connecting the interfaces for the inverter control
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF