Installing
3.4 Mounting the Power Modules
Power Module PM240-2
36
Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 3- 8
Dimensions depend on the Control Unit (CU) and HMI device [mm]
Frame
size
Width
[mm]
Height [mm]
Overall depth in the cabinet [mm]
Without
shield
plate
With shield
plate
T1
with
CU230P-
2
1)
with
CU240B-2
1)
/
CU240E-2
1)
with
CU250S-
2
1)
FSD
275
517
650
141
155
141
158
FSE
354
615
772
141
155
141
158
FSF
384
785
1021
177.5
193
177.5
196
1)
With a Smart Access Module plus 9 mm
With blanking cover or with Operator Panel plus 11 mm.
Table 3- 9
Cooling air clearances, further dimensions and mounting
Frame
size
Power Module depth [mm]
Cooling air clearances [mm]
Fixing/torque
[Nm]
T1 + T2
T1
T2
Top
Bottom
Front
FSD
238.5
141
97.5
350
300
100
10 × M5 / 3.5
FSE
238.5
141
97.5
350
300
100
10 × M5 / 3.5
FSF
358
177.5 180.5
350
300
100
12 × M6 / 5.9
3.4.4
Mounting the shield plates
Use the provided shield plate for strain relief of the line and motor cable – as well as the
shield support for the motor cable.
The shield plates and fixings screws are included in the converter accessory kit.
Mounting the shield plate, FSA ... FSC - Built-in devices
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......