Technical data
8.4 Technical data, PM240 Power Modules
Frequency inverter
226
Operating Instructions, 08.10. 2008, t.b.d.
8.4
Technical data, PM240 Power Modules
General conditions
The input currents specified for the PM240 Power Modules is the technical data apply for a
400V line supply with U
k
= 1% referred to the frequency inverter power rating. When using a
line reactor, the currents are reduced by a few percent.
Table 8- 1
PM240 Frame Size A
Order No.
6SL3224-0BE13-
7UA0
6SL3224-0BE15-
5UA0
6SL3224-0BE17-
5UA0
6SL3224-0BE21-
1UA0
6SL3224-0BE21-
5UA0
Power rating for HO
base load
0.37 kW / 0.5 PS 0.55 kW / 0.75 PS
0.75 kW / 1 PS
1.1 kW / 1.5 PS
1.5 kW / 2 PS
Input current for HO
base load
1.6 A
2.0 A
2.5 A
3.8
4.8
Output current for
HO base load
1.3 A
1.7 A
2.2 A
3.1
4.1
Fuse
10 A
10 A
10 A
10 A
10 A
Heat loss
0.097 kW
0.099 kW
0.102 kW
0.108
0.114
Cooling air
requirement
4.8 l/s / 10 CFM
4.8 l/s / 10 CFM
4.8 l/s / 10 CFM
4.8 l/s / 10 CFM
4.8 l/s / 10 CFM
Cable cross-section
for line and motor
connections
1 … 2.5 mm
2
/
18 … 14 AWG
1 … 2.5 mm
2
/
18 … 14 AWG
1 … 2.5 mm
2
/
18 … 14 AWG
1 … 2.5 mm
2
/
18 … 14 AWG
1 … 2.5 mm
2
/
18 … 14 AWG
Weight
1.2 kg / 2.6 lb
1.2 kg / 2.6 lb
1.2 kg / 2.6 lb
1.2 kg / 2.6 lb
1.2 kg / 2.6 lb