Functions
5.12 Safety-related applications
Frequency inverter
202
Operating Instructions, 08.10. 2008, t.b.d.
5.12.4
Settings for the "STO" function
Activating fail-safe inputs
A fail-safe input of the frequency inverter is activated by assigning it a safety function. This is
described in the following using an example. The example shows the assignment of the fail-
safe digital input FDI0 to the STO safety function using STARTER.
Procedure
1.
Connect your PC to the frequency inverter e.g. using the PC Connection Kit.
2.
Launch the STARTER parameterization tool and go online.
3.
In STARTER, call the screens with the fail-safe functions