Functions
5.11 Operation in fieldbus systems
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
171
5.11.2.3
Integrating a frequency inverter in PROFINET
Assignment of the RJ45 connector to integrate a frequency inverter into PROFINET
The CU240S PN and CU240S PN-F Control Units are equipped with an Ethernet switch for
two connections in the form of RJ45 sockets. Connections with optical networks are
established via switches, which are equipped with an electrical and optical port. The drive is
then connected to an electrical port, which means that no power supply is available for an
external electrical/optical converter.
Table 5- 58 Contact assignment of the RJ45 sockets
Contact Designation
Meaning
Wire color
1
TX+
Transmit data +
Yellow
2
TX
Transmit data -
Orange
3
RX+
Receive data +
White
4
-
5
-
6
RX -
Receive data -
Blue
For information about assembling the SIMATIC NET Industrial Ethernet FastConnect RF45
plug 180, see "Assembly Instructions for SIMATIC NET Industrial Ethernet FastConnect
RJ45 Plug". The document can be downloaded from the following page:
http://support.automation.siemens.com/WW/view/en/23175326/130000
Recommended PROFINET connectors
We recommend the following connector for the PROFINET cable:
6GK1901-1BB10-2Ax0
Permissible cable length / installing and shielding the PROFINET cable
For information about this, see
http://support.automation.siemens.com/WW/view/de/25571355.
Note
SINAMICS does not support routing between PROFIBUS and PROFINET (and vice versa).